I-1054 Isolater Module

I-1054 addressbale zone monitor unit is designed and developed to fully compatible with I-1000-1 fire panels. It is used to protect circuit shortcut. It isolates the shortcut from the loop and protects othe detectors and equipment. It powers from the loop and there is no use limit of isolater for the loop. It doesnt use address. It allows loop continue working when there is a shortcut between two isolators. In case of failure indicator is on permanently.

Specifications

  • Intelligent detection and communication protocols,
  • High quality and reliability,
  • SMD design
  • No limit of use
  • Powered by loop
  • Operation LED indicator
  • Esthetic design
  • Enclosure and Color: ABS, red
  • 2 year warranty
  • Weight ~ : 120 gr
TECHNICAL SPECIFICATIONS

Standard:

EN54

Protection level:

IP33

Operating Voltage:

24V DC loop voltage(+-%10)

Operating Current:

50mA Max,  3 mA Min

Operating Temperature:

-10oC +50oC

Indicators:

Yellow : Failure

Enclosure and Color:

ABS, Red

Cable:

1 double pole and supply cable

Dimensions:

Dia.:120mm*80mm*40mm

Weight: ~

150 gr